Specifications Table for RYYQ-U5

RYYQ22U5Y1B RYYQ24U5Y1B RYYQ26U5Y1B RYYQ30U5Y1B RYYQ32U5Y1B RYYQ34U5Y1B RYYQ36U5Y1B RYYQ38U5Y1B RYYQ40U5Y1B RYYQ42U5Y1B RYYQ44U5Y1B RYYQ46U5Y1B RYYQ48U5Y1B RYYQ50U5Y1B RYYQ52U5Y1B RYYQ54U5Y1B
Sound pressure level Cooling Nom. dBA 62.5 (5) 64.0 (5) 63.5 (5) 64.5 (5) 66.0 (5) 65.5 (5) 67.1 (5) 66.2 (5) 65.2 (5) 66.5 (5) 67.2 (5) 67.0 (5) 67.8 (5) 67.5 (5) 67.1 (5) 66.8 (5)
Standard Accessories Installation manual 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
  Operation manual 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
  Connection pipes 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
SEER recommended combination 2 6.7 6.6 6.5 6.3 6.3 6.3 6.3 6.8 6.6 6.6 6.3 6.4 6.3 6.3 6.4 6.4
SEER recommended combination 3 6.9 6.7 6.6 6.5 6.2 6.3 6.3 6.9 6.7 6.5 6.3 6.3 6.2 6.3 6.4 6.4
Capacity range HP 22 24 26 30 32 34 36 38 40 42 44 46 48 50 52 54
ηs,c % 274.5 269.9 264.2 256.8 251.7 253.3 250.8 272.4 263.5 261.2 255.9 254.9 251.7 252.8 253.7 254.1
Maximum number of connectable indoor units 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3)
Space cooling B Condition (30°C - 27/19) Pdc kW 45.3 49.7 54.2 61.8 66.3 70.3 71.5 75.5 82.5 86.9 91.0 95.8 99.5 103.4 107.4 111.4
    EERd   4.8 4.6 4.6 4.3 4.3 4.2 4.1 4.5 4.5 4.4 4.4 4.4 4.3 4.2 4.2 4.1
  D Condition (20°C - 27/19) Pdc kW 18.8 15.8 16.2 21.0 19.0 20.1 20.4 21.6 23.6 24.8 26.0 27.4 28.4 29.6 30.7 34.4
    EERd   16.0 15.2 14.2 16.8 14.3 16.8 16.7 17.9 16.0 15.4 14.4 14.3 14.3 15.9 17.6 19.1
  A Condition (35°C - 27/19) EERd   2.6 2.5 2.6 2.1 2.3 2.1 2.1 2.4 2.2 2.3 2.3 2.4 2.3 2.1 2.0 1.9
    Pdc kW 61.5 67.4 73.5 83.9 90.0 95.4 97.0 102.4 111.9 118.0 123.5 130.0 135.0 140.4 145.8 151.2
  C Condition (25°C - 27/19) EERd   8.5 8.6 8.2 8.2 8.1 8.1 7.9 8.5 8.3 8.2 8.1 8.1 8.1 8.1 8.1 8.1
    Pdc kW 29.1 31.9 34.8 39.7 42.6 45.2 45.9 48.5 53.0 55.9 58.5 61.6 64.0 66.5 69.1 71.6
SCOP 4.4 4.3 4.2 4.3 4.2 4.2 4.1 4.3 4.3 4.2 4.2 4.1 4.1 4.2 4.3 4.3
Refrigerant GWP   2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
  Type   R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
Space cooling recommended combination 3 B Condition (30°C - 27/19) Pdc kW 45.3 49.7 54.2 61.8 66.3 70.3 71.5 75.5 82.5 87.0 91.0 95.8 99.5 103.5 107.4 111.4
    EERd   4.8 4.5 4.5 4.3 4.1 4.1 4.0 4.5 4.4 4.3 4.3 4.2 4.1 4.1 4.1 4.1
  D Condition (20°C - 27/19) Pdc kW 18.8 15.7 16.0 21.0 19.0 20.1 20.4 21.6 23.6 24.8 26.0 27.4 28.4 29.6 30.7 34.7
    EERd   15.8 15.2 14.0 16.6 13.8 16.6 16.5 17.9 16.1 15.2 14.2 13.9 13.8 15.6 17.5 19.1
  A Condition (35°C - 27/19) EERd   2.5 2.5 2.5 2.1 2.2 2.1 2.1 2.4 2.2 2.3 2.3 2.3 2.2 2.1 2.0 1.9
    Pdc kW 61.5 67.4 73.5 83.9 90.0 95.4 97.0 102.4 111.9 118.0 123.5 130.0 135.0 140.4 145.8 151.2
  C Condition (25°C - 27/19) EERd   8.5 8.4 8.1 8.2 7.8 8.0 7.8 8.5 8.4 8.0 7.9 7.9 7.8 7.9 8.0 8.2
    Pdc kW 29.1 31.9 34.8 39.7 42.6 45.2 45.9 48.5 53.0 55.9 58.5 61.6 63.9 66.5 69.1 71.6
SCOP recommended combination 3 4.3 4.2 4.2 4.3 4.1 4.2 4.1 4.2 4.3 4.2 4.2 4.1 4.1 4.2 4.2 4.2
Space cooling recommended combination 2 C Condition (25°C - 27/19) Pdc kW 29.1 31.9 34.8 39.7 42.6 45.2 45.9 48.5 53.0 55.9 58.5 61.6 63.9 66.5 69.0 71.6
    EERd   8.2 8.4 7.9 7.9 8.0 8.1 7.9 8.4 8.1 8.2 7.9 8.1 8.0 8.0 8.1 8.1
  A Condition (35°C - 27/19) EERd   2.6 2.4 2.6 2.1 2.2 2.1 2.1 2.3 2.2 2.3 2.3 2.3 2.2 2.1 2.0 1.9
    Pdc kW 61.5 67.4 73.5 83.9 90.0 95.4 97.0 102.4 111.9 118.0 123.5 130.0 135.0 140.4 145.8 151.2
  D Condition (20°C - 27/19) EERd   15.6 14.7 13.6 16.1 14.0 16.5 16.5 17.8 15.9 15.3 14.0 14.0 14.0 15.6 17.4 18.9
    Pdc kW 18.4 15.4 15.7 20.5 18.9 20.1 20.4 21.6 23.6 24.8 26.0 27.4 28.4 29.6 30.7 34.1
  B Condition (30°C - 27/19) EERd   4.6 4.5 4.4 4.2 4.2 4.2 4.1 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.1
    Pdc kW 45.3 49.7 54.1 61.8 66.3 70.3 71.5 75.4 82.4 86.9 91.0 95.8 99.5 103.5 107.4 111.4
System Outdoor unit module 2   RYMQ12U RYMQ16U RYMQ14U RYMQ18U RYMQ16U RYMQ18U RYMQ20U RYMQ10U RYMQ12U RYMQ16U RYMQ16U RYMQ16U RYMQ16U RYMQ16U RYMQ18U RYMQ18U
  Outdoor unit module 3                 RYMQ20U RYMQ18U RYMQ16U RYMQ16U RYMQ16U RYMQ16U RYMQ18U RYMQ18U RYMQ18U
  Outdoor unit module 1   RYMQ10U RYMQ8U RYMQ12U RYMQ12U RYMQ16U RYMQ16U RYMQ16U RYMQ8U RYMQ10U RYMQ10U RYMQ12U RYMQ14U RYMQ16U RYMQ16U RYMQ16U RYMQ18U
Recommended combination 3 6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB 4 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 7 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 9 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 8 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 3 x FXMQ50P7VEB + 9 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 2 x FXMQ50P7VEB + 10 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 6 x FXMQ50P7VEB + 10 x FXMQ63P7VEB 9 x FXMQ50P7VEB + 9 x FXMQ63P7VEB 12 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 6 x FXMQ50P7VEB + 8 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 1 x FXMQ50P7VEB + 13 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 12 x FXMQ63P7VEB + 6 x FXMQ80P7VEB 3 x FXMQ50P7VEB + 13 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 6 x FXMQ50P7VEB + 14 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 9 x FXMQ50P7VEB + 15 x FXMQ63P7VEB
Recommended combination 2 6 x FXSQ50A2VEB + 4 x FXSQ63A2VEB 4 x FXSQ50A2VEB + 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 7 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 9 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 8 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 3 x FXSQ50A2VEB + 9 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 2 x FXSQ50A2VEB + 10 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 6 x FXSQ50A2VEB + 10 x FXSQ63A2VEB 9 x FXSQ50A2VEB + 9 x FXSQ63A2VEB 12 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 6 x FXSQ50A2VEB + 8 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 1 x FXSQ50A2VEB + 13 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 12 x FXSQ63A2VEB + 6 x FXSQ80A2VEB 3 x FXSQ50A2VEB + 13 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 6 x FXSQ50A2VEB + 14 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 9 x FXSQ50A2VEB + 15 x FXSQ63A2VEB
SCOP recommended combination 2 4.4 4.3 4.2 4.3 4.2 4.3 4.2 4.3 4.4 4.3 4.2 4.2 4.2 4.2 4.3 4.3
Power input - 50Hz Heating Nom. 6°CWB kW 17.23 (2) 17.94 (2) 20.33 (2) 23.87 (2) 25.08 (2) 26.76 (2) 30.02 (2) 30.45 (2) 31.45 (2) 32.66 (2) 34.73 (2) 35.77 (2) 37.62 (2) 39.30 (2) 40.98 (2) 42.66 (2)
Indoor index connection Min.   275.0 300.0 325.0 375.0 400.0 425.0 450.0 475.0 500.0 525.0 550.0 575.0 600.0 625.0 650.0 675.0
  Max.   715.0 780.0 845.0 975.0 1,040.0 1,105.0 1,170.0 1,235.0 1,300.0 1,365.0 1,430.0 1,495.0 1,560.0 1,625.0 1,690.0 1,755.0
Cooling capacity Prated,c kW 61.5 (1) 67.4 (1) 73.5 (1) 83.9 (1) 90.0 (1) 95.4 (1) 97.0 (1) 102.4 (1) 111.9 (1) 118.0 (1) 123.5 (1) 130.0 (1) 135.0 (1) 140.4 (1) 145.8 (1) 151.2 (1)
COP at nom. capacity 6°CWB kW/kW 3.57 (2) 3.76 (2) 3.61 (2) 3.51 (2) 3.59 (2) 3.56 (2) 3.36 (2) 3.49 (2) 3.56 (2) 3.61 (2) 3.56 (2) 3.63 (2) 3.59 (2) 3.57 (2) 3.56 (2) 3.54 (2)
Recommended combination 6 x FXFQ50AVEB + 4 x FXFQ63AVEB 4 x FXFQ50AVEB + 4 x FXFQ63AVEB + 2 x FXFQ80AVEB 7 x FXFQ50AVEB + 5 x FXFQ63AVEB 9 x FXFQ50AVEB + 5 x FXFQ63AVEB 8 x FXFQ63AVEB + 4 x FXFQ80AVEB 3 x FXFQ50AVEB + 9 x FXFQ63AVEB + 2 x FXFQ80AVEB 2 x FXFQ50AVEB + 10 x FXFQ63AVEB + 2 x FXFQ80AVEB 6 x FXFQ50AVEB + 10 x FXFQ63AVEB 9 x FXFQ50AVEB + 9 x FXFQ63AVEB 12 x FXFQ63AVEB + 4 x FXFQ80AVEB 6 x FXFQ50AVEB + 8 x FXFQ63AVEB + 4 x FXFQ80AVEB 1 x FXFQ50AVEB + 13 x FXFQ63AVEB + 4 x FXFQ80AVEB 12 x FXFQ63AVEB + 6 x FXFQ80AVEB 3 x FXFQ50AVEB + 13 x FXFQ63AVEB + 4 x FXFQ80AVEB 6 x FXFQ50AVEB + 14 x FXFQ63AVEB + 2 x FXFQ80AVEB 9 x FXFQ50AVEB + 15 x FXFQ63AVEB
Space heating (Average climate) TOL COPd (declared COP)   2.3 2.5 2.3 2.1 2.4 2.2 2.1 2.2 2.2 2.4 2.3 2.4 2.4 2.3 2.2 2.1
    Pdh (declared heating cap) kW 34.4 36.9 39.0 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    Tol (temperature operating limit) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  D Condition (12°C) Pdh (declared heating cap) kW 6.0 5.7 6.0 7.1 7.1 7.9 8.3 13.1 13.1 9.9 10.0 10.3 10.7 12.0 14.2 14.2
    COPd (declared COP)   8.2 8.9 8.8 9.0 9.0 8.8 8.6 8.7 8.7 8.6 8.6 8.7 8.8 8.9 9.0 9.0
  B Condition (2°C) COPd (declared COP)   4.0 3.7 3.8 3.9 3.6 3.7 3.7 3.9 4.0 3.7 3.7 3.6 3.6 3.7 3.8 3.9
    Pdh (declared heating cap) kW 18.5 19.9 21.0 24.9 25.0 27.5 29.2 32.7 33.5 33.6 34.9 36.1 37.5 40.0 42.5 45.1
  C Condition (7°C) COPd (declared COP)   6.3 6.3 6.1 6.5 6.3 6.5 6.4 6.5 6.5 6.3 6.3 6.2 6.3 6.5 6.6 6.8
    Pdh (declared heating cap) kW 11.9 13.0 13.5 16.0 16.1 17.7 18.8 21.3 21.6 21.6 22.4 23.2 24.1 25.7 27.4 29.0
  A Condition (-7°C) COPd (declared COP)   2.6 2.8 2.6 2.6 2.7 2.6 2.5 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.6 2.6
    Pdh (declared heating cap) kW 30.4 32.6 34.5 41.0 41.0 45.2 47.9 53.7 55.1 55.2 57.3 59.3 61.6 65.7 69.9 74.0
  TBivalent Pdh (declared heating cap) kW 34.4 36.9 39.0 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    Tbiv (bivalent temperature) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
    COPd (declared COP)   2.3 2.5 2.3 2.1 2.4 2.2 2.1 2.2 2.2 2.4 2.3 2.4 2.4 2.3 2.2 2.1
Piping connections Liquid OD mm 15.9 15.9 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1
    Type   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
  Total piping length System Actual m 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6)
  Gas OD mm 28.6 34.9 34.9 34.9 34.9 34.9 41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3
    Type   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
SEER 6.9 6.8 6.7 6.5 6.4 6.4 6.3 6.9 6.7 6.6 6.5 6.4 6.4 6.4 6.4 6.4
Space heating (Average climate) recommended combination 2 B Condition (2°C) Pdh (declared heating cap) kW 18.5 19.9 21.0 24.9 25.0 27.5 29.2 32.7 33.5 33.6 34.9 36.1 37.5 40.0 42.6 45.1
    COPd (declared COP)   4.1 3.7 3.8 3.9 3.6 3.8 3.7 3.9 4.0 3.7 3.7 3.6 3.6 3.7 3.8 3.9
  C Condition (7°C) Pdh (declared heating cap) kW 11.9 13.1 13.1 16.0 16.1 17.7 18.8 21.3 21.6 21.6 22.4 22.8 24.1 25.7 27.4 29.0
    COPd (declared COP)   6.3 6.3 6.1 6.6 6.3 6.6 6.5 6.5 6.5 6.4 6.3 6.3 6.3 6.5 6.7 6.8
  A Condition (-7°C) COPd (declared COP)   2.6 2.7 2.6 2.6 2.7 2.6 2.5 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.6 2.6
    Pdh (declared heating cap) kW 30.4 32.6 34.5 41.0 41.0 45.2 47.9 53.7 55.1 55.2 57.3 59.3 61.6 65.7 69.9 74.0
  TOL Pdh (declared heating cap) kW 34.4 36.9 39.0 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    COPd (declared COP)   2.2 2.4 2.2 2.1 2.4 2.2 2.2 2.3 2.2 2.4 2.3 2.4 2.4 2.3 2.2 2.1
    Tol (temperature operating limit) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  D Condition (12°C) Pdh (declared heating cap) kW 6.0 5.7 6.0 7.2 7.1 7.9 8.3 13.2 13.2 10.0 10.0 10.3 10.7 12.2 14.4 14.4
    COPd (declared COP)   8.4 9.0 8.9 9.1 9.1 8.9 8.8 8.8 8.8 8.7 8.7 8.8 8.9 9.0 9.1 9.1
  TBivalent Pdh (declared heating cap) kW 34.4 36.9 39.0 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    COPd (declared COP)   2.2 2.4 2.2 2.1 2.4 2.2 2.2 2.3 2.2 2.4 2.3 2.4 2.4 2.3 2.2 2.1
    Tbiv (bivalent temperature) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
Space heating (Average climate) recommended combination 3 B Condition (2°C) Pdh (declared heating cap) kW 18.5 19.9 21.0 24.9 25.0 27.5 29.2 32.7 33.5 33.6 34.9 36.1 37.5 40.0 42.5 45.1
    COPd (declared COP)   4.0 3.7 3.8 3.9 3.6 3.7 3.6 3.8 3.9 3.7 3.7 3.6 3.6 3.6 3.7 3.8
  C Condition (7°C) COPd (declared COP)   6.2 6.3 6.1 6.3 6.3 6.4 6.3 6.3 6.4 6.3 6.2 6.2 6.3 6.4 6.4 6.5
    Pdh (declared heating cap) kW 11.9 12.9 13.5 16.0 16.1 17.7 18.8 21.2 21.6 21.6 22.4 23.2 24.1 25.7 27.3 29.0
  A Condition (-7°C) Pdh (declared heating cap) kW 30.4 32.6 34.5 41.0 41.0 45.2 47.9 53.7 55.1 55.2 57.3 59.3 61.6 65.7 69.9 74.0
    COPd (declared COP)   2.6 2.7 2.6 2.5 2.7 2.6 2.4 2.5 2.6 2.7 2.6 2.7 2.7 2.6 2.6 2.5
  TOL Pdh (declared heating cap) kW 34.4 36.9 39.0 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    Tol (temperature operating limit) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
    COPd (declared COP)   2.3 2.4 2.2 2.1 2.4 2.2 2.1 2.2 2.2 2.4 2.3 2.4 2.4 2.2 2.2 2.1
  D Condition (12°C) COPd (declared COP)   8.2 8.9 8.8 8.6 9.0 8.9 8.3 8.5 8.4 8.6 8.6 8.7 8.8 8.7 8.7 8.7
    Pdh (declared heating cap) kW 6.0 5.7 6.0 7.1 7.1 7.9 8.3 12.9 12.8 9.9 10.0 10.3 10.7 11.8 13.7 13.7
  TBivalent Pdh (declared heating cap) kW 34.4 36.9 39.0 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    COPd (declared COP)   2.3 2.4 2.2 2.1 2.4 2.2 2.1 2.2 2.2 2.4 2.3 2.4 2.4 2.2 2.2 2.1
    Tbiv (bivalent temperature) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
Sound power level Cooling Nom. dBA 84.8 (4) 86.3 (4) 85.3 (4) 86.6 (4) 88.6 (4) 87.8 (4) 89.9 (4) 88.8 (4) 87.3 (4) 89.1 (4) 89.8 (4) 89.3 (4) 90.4 (4) 89.8 (4) 89.3 (4) 88.6 (4)
ηs,h % 171.2 167.0 164.6 169.8 163.1 166.2 162.4 167.5 170.0 165.5 164.5 162.0 162.8 165.2 167.2 169.4
Continuous heating Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Heating capacity Prated,h kW 61.5 (2) 67.4 (2) 73.5 (2) 83.9 (2) 90.0 (2) 95.4 (2) 101.0 (2) 106.4 (2) 111.9 (2) 118.0 (2) 123.5 (2) 130.0 (2) 135.0 (2) 140.4 (2) 145.8 (2) 151.2 (2)
  Nom. 6°CWB kW 61.5 (2) 67.4 (2) 73.5 (2) 83.9 (2) 90.0 (2) 95.4 (2) 101.0 (2) 106.4 (2) 111.9 (2) 118.0 (2) 123.5 (2) 130.0 (2) 135.0 (2) 140.4 (2) 145.8 (2) 151.2 (2)
Power supply Phase   3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~
  Name   Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1
  Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%)
  (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates.
  (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
  (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual
  (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
  (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
  (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
  (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan
  (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%.
  (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (15) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature )
  (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (16) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality
  (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room. (17) - Sound values are measured in a semi-anechoic room.
  (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (18) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
  (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
  (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power (20) - Ssc: Short-circuit power
  (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual (21) - For detailed contents of standard accessories, see installation/operation manual
  (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination (22) - Multi combination (22~54HP) data is corresponding with the standard multi combination