Specifications Table for RWEYQ-P

RWEYQ8PY1 RWEYQ10PY1 RWEYQ16PY1 RWEYQ18PY1 RWEYQ20PY1 RWEYQ24PY1 RWEYQ26PY1 RWEYQ28PY1 RWEYQ30PY1
Sound pressure level Cooling Nom. dBA 50 51 53 54 54 55 55 55 56
Standard Accessories Installation manual Installation manual Installation manual
  Operation manual Operation manual Operation manual
  Connection pipes Connection pipes Connection pipes
  Clamps Clamps Clamps
Capacity range HP 8 10 16 18 20 24 26 28 30
Maximum number of connectable indoor units 17 21 34 36 36 36 36 36 36
Compressor Type   Hermetically sealed scroll compressor Hermetically sealed scroll compressor
Weight Unit kg 149 150
EER 4.89 4.14 4.92 4.63 4.41 4.91 4.74 4.57 4.43
Refrigerant Charge TCO2Eq 7.3 8.8
  GWP   2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
  Charge kg 3.5 4.2
  Type   R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
System Outdoor unit module 2       RWEYQ8PY1 RWEYQ8PY1 RWEYQ10PY1 RWEYQ8PY1 RWEYQ8PY1 RWEYQ10PY1 RWEYQ10PY1
  Outdoor unit module 3             RWEYQ8PY1 RWEYQ8PY1 RWEYQ8PY1 RWEYQ10PY1
  Outdoor unit module 1   RWEYQ8PY1 RWEYQ10PY1 RWEYQ8PY1 RWEYQ10PY1 RWEYQ10PY1 RWEYQ8PY1 RWEYQ10PY1 RWEYQ10PY1 RWEYQ10PY1
Power input - 50Hz Cooling Nom. kW 4.55 6.03 9.10 10.6 12.1 13.7 15.1 16.6 18.1
  Heating Nom. kW 4.24 6.05 8.48 10.3 12.1 12.7 14.5 16.3 18.2
Indoor index connection Nom.   200 250 400 450 500 600 650 700 750
  Min.   100 125 200 225 250 300 325 350 375
  Max.   260 325 520 585 650 780 845 910 975
Cooling capacity Nom. kW 22.4 (1) 26.7 (1) 44.8 (1) 49.1 (1) 53.4 (1) 67.2 (1) 71.5 (1) 75.8 (1) 80.1 (1)
Piping connections Liquid OD mm 9.52 9.52 12.7 15.9 15.9 15.9 19.1 19.1 19.1
    Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection
  Total piping length System Actual m 300 300 300 300 300 300 300 300 300
  Gas OD mm 19.1 (3) 22.2 (3) 28.6 (3) 28.6 (3) 28.6 (3) 34.9 (3) 34.9 (3) 34.9 (3) 34.9 (3)
    Type   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
  Drain Outlet   PS 1/2B internal thread PS 1/2B internal thread
  Level difference OU - IU Outdoor unit in highest position m 50 50 50 50 50 50 50 50 50
      Indoor unit in highest position m 40 40 40 40 40 40 40 40 40
    IU - IU Max. m 15 15 15 15 15 15 15 15 15
  Discharge gas OD mm 15.9 (4), 19.1 (5) 19.1 (4), 22.2 (5) 22.2 (4), 28.6 (5) 22.2 (4), 28.6 (5) 22.2 (4), 28.6 (5) 28.6 (4), 34.9 (5) 28.6 (4), 34.9 (5) 28.6 (4), 34.9 (5) 28.6 (4), 34.9 (5)
    Type   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
  Water Inlet   PT1 1/4B internal thread PT1 1/4B internal thread
    Outlet   PT1 1/4B internal thread PT1 1/4B internal thread
COP 5.81 5.08 5.87 5.48 5.21 5.91 5.62 5.40 5.19
Dimensions Unit Width mm 780 780
    Depth mm 550 550
    Height mm 1,000 1,000
Heating capacity Nom. kW 25.0 (2) 31.5 (2) 50.0 (2) 56.5 (2) 63.0 (2) 75.0 (2) 81.5 (2) 88.0 (2) 94.5 (2)
Power supply Phase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Name   Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1
  Frequency Hz 50 50 50 50 50 50 50 50 50
  Voltage V 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m.
  (2) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m
  (3) - In case of heat pump system, gas pipe is not used (3) - In case of heat pump system, gas pipe is not used (3) - In case of heat pump system, gas pipe is not used (3) - In case of heat pump system, gas pipe is not used (3) - In case of heat pump system, gas pipe is not used (3) - In case of heat pump system, gas pipe is not used (3) - In case of heat pump system, gas pipe is not used (3) - In case of heat pump system, gas pipe is not used (3) - In case of heat pump system, gas pipe is not used
  (4) - In case of heat recovery system (4) - In case of heat recovery system (4) - In case of heat recovery system (4) - In case of heat recovery system (4) - In case of heat recovery system (4) - In case of heat recovery system (4) - In case of heat recovery system (4) - In case of heat recovery system (4) - In case of heat recovery system
  (5) - In case of heat pump system (5) - In case of heat pump system (5) - In case of heat pump system (5) - In case of heat pump system (5) - In case of heat pump system (5) - In case of heat pump system (5) - In case of heat pump system (5) - In case of heat pump system (5) - In case of heat pump system
  (6) - This unit should not be installed outdoors, but indoors e.g. in a machine room. (6) - This unit should not be installed outdoors, but indoors e.g. in a machine room. (6) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (6) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (6) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (6) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (6) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (6) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (6) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C
  (7) - Hold ambient temperature at 0-40°C and humidity at 80%RH or less. Heat rejection from the casing: 0.64kW/8HP (7) - Hold ambient temperature at 0-40°C and humidity at 80%RH or less. Heat rejection from the casing: 0.71kW/10HP (7) - TOCA means the total value of each OC set. (7) - TOCA means the total value of each OC set. (7) - TOCA means the total value of each OC set. (7) - TOCA means the total value of each OC set. (7) - TOCA means the total value of each OC set. (7) - TOCA means the total value of each OC set. (7) - TOCA means the total value of each OC set.
  (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C (8) - MSC means the maximum current during start up of the compressor (8) - MSC means the maximum current during start up of the compressor (8) - MSC means the maximum current during start up of the compressor (8) - MSC means the maximum current during start up of the compressor (8) - MSC means the maximum current during start up of the compressor (8) - MSC means the maximum current during start up of the compressor (8) - MSC means the maximum current during start up of the compressor
  (9) - TOCA means the total value of each OC set. (9) - TOCA means the total value of each OC set. (9) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (9) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (9) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (9) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (9) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (9) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (9) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (10) - MSC means the maximum current during start up of the compressor (10) - MSC means the maximum current during start up of the compressor (10) - Maximum allowable voltage range variation between phases is 2%. (10) - Maximum allowable voltage range variation between phases is 2%. (10) - Maximum allowable voltage range variation between phases is 2%. (10) - Maximum allowable voltage range variation between phases is 2%. (10) - Maximum allowable voltage range variation between phases is 2%. (10) - Maximum allowable voltage range variation between phases is 2%. (10) - Maximum allowable voltage range variation between phases is 2%.
  (11) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (11) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (11) - Select wire size based on the value of MCA (11) - Select wire size based on the value of MCA (11) - Select wire size based on the value of MCA (11) - Select wire size based on the value of MCA (11) - Select wire size based on the value of MCA (11) - Select wire size based on the value of MCA (11) - Select wire size based on the value of MCA
  (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (13) - Select wire size based on the value of MCA (13) - Select wire size based on the value of MCA (13) - Refer to refrigerant pipe selection or installation manual (13) - Refer to refrigerant pipe selection or installation manual (13) - Refer to refrigerant pipe selection or installation manual (13) - Refer to refrigerant pipe selection or installation manual (13) - Refer to refrigerant pipe selection or installation manual (13) - Refer to refrigerant pipe selection or installation manual (13) - Refer to refrigerant pipe selection or installation manual
  (14) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (14) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (14) - Contains fluorinated greenhouse gases (14) - Contains fluorinated greenhouse gases (14) - Contains fluorinated greenhouse gases (14) - Contains fluorinated greenhouse gases (14) - Contains fluorinated greenhouse gases (14) - Contains fluorinated greenhouse gases (14) - Contains fluorinated greenhouse gases
  (15) - Refer to refrigerant pipe selection or installation manual (15) - Refer to refrigerant pipe selection or installation manual
  (16) - Contains fluorinated greenhouse gases (16) - Contains fluorinated greenhouse gases