Specifications Table for REYA-A9

REYA10A7Y1B9. REYA13A7Y1B9 REYA8A7Y1B9 REYA10A7Y1B9 REYA12A7Y1B9 REYA14A7Y1B9 REYA16A7Y1B9. REYA16A7Y1B9 REYA18A7Y1B9. REYA18A7Y1B9 REYA20A7Y1B9. REYA20A7Y1B9 REYA22A7Y1B9 REYA24A7Y1B9 REYA26A7Y1B9 REYA28A7Y1B9
System Outdoor unit module 1   REMA5A9 REMA5A9         REYA8A9   REYA8A9   REYA8A9   REYA10A9 REYA8A9 REYA12A9 REYA12A9
  Outdoor unit module 2   REMA5A9 REYA8A9         REYA8A9   REYA10A9   REYA12A9   REYA12A9 REYA16A9 REYA14A9 REYA16A9
Recommended combination 4 x FXFA63A2VEB 3 x FXFA50A2VEB + 3 x FXFA63A2VEB 4 x FXFA50A2VEB 4 x FXFA63A2VEB 6 x FXFA50A2VEB 1 x FXFA50A2VEB + 5 x FXFA63A2VEB 4 x FXFA63A2VEB + 2 x FXFA80A2VEB 4 x FXFA63A2VEB + 2 x FXFA80A2VEB 4 x FXFA50A2VEB + 4 x FXFA63A2VEB 3 x FXFA50A2VEB + 5 x FXFA63A2VEB 10 x FXFA50A2VEB 8 x FXFA63A2VEB 6 x FXFA50A2VEB + 4 x FXFA63A2VEB 4 x FXFA50A2VEB + 4 x FXFA63A2VEB + 2 x FXFA80A2VEB 7 x FXFA50A2VEB + 5 x FXFA63A2VEB 6 x FXFA50A2VEB + 4 x FXFA63A2VEB + 2 x FXFA80A2VEB
Recommended combination 2 4 x FXSA63A2VEB 3 x FXSA50A2VEB + 3 x FXSA63A2VEB 4 x FXSA50A2VEB 4 x FXSA63A2VEB 6 x FXSA50A2VEB 1 x FXSA50A2VEB + 5 x FXSA63A2VEB 4 x FXSA63A2VEB + 2 x FXSA80A2VEB 4 x FXSA63A2VEB + 2 x FXSA80A2VEB 4 x FXSA50A2VEB + 4 x FXSA63A2VEB 3 x FXSA50A2VEB + 5 x FXSA63A2VEB 10 x FXSA50A2VEB 8 x FXSA63A2VEB 6 x FXSA50A2VEB + 4 x FXSA63A2VEB 4 x FXSA50A2VEB + 4 x FXSA63A2VEB + 2 x FXSA80A2VEB 7 x FXSA50A2VEB + 5 x FXSA63A2VEB 6 x FXSA50A2VEB + 4 x FXSA63A2VEB + 2 x FXSA80A2VEB
Recommended combination 3 4 x FXMA63A5VEB 3 x FXMA50A5VEB + 3 x FXMA50A5VEB 4 x FXMA50A5VEB 4 x FXMA63A5VEB 6 x FXMA50A5VEB 1 x FXMA50A5VEB + 5 x FXMA63A5VEB 4 x FXMA63A5VEB + 2 x FXMA80A5VEB 4 x FXMA63A5VEB + 2 x FXMA80A5VEB 4 x FXMA50A5VEB + 4 x FXMA63A5VEB 3 x FXMA50A5VEB + 5 x FXMA63A5VEB 10 x FXMA50A5VEB 8 x FXMA63A5VEB 6 x FXMA50A5VEB + 4 x FXMA63A5VEB 4 x FXMA50A5VEB + 4 x FXMA63A5VEB + 2 x FXMA80A5VEB 7 x FXMA50A5VEB + 5 x FXMA63A5VEB 6 x FXMA50A5VEB + 4 x FXMA63A5VEB + 2 x FXMA80A5VEB
Continuous heating Yes Yes         Yes   Yes   Yes   Yes Yes Yes Yes
Cooling capacity Prated,c kW 28.0 (1) 36.4 (1) 22.4 (1) 28.0 (1) 33.5 (1) 40.0 (1) 44.8 (1) 45.0 (1) 50.4 (1) 50.4 (1) 55.9 (1) 56.0 (1) 61.5 (1) 67.4 (1) 73.5 (1) 78.5 (1)
Heating capacity Prated,h kW 28.0 (2) 36.4 (2) 22.4 (2) 28.0 (2) 33.5 (2) 40.0 (2) 44.8 (2) 45.0 (2) 50.4 (2) 50.4 (2) 55.9 (2) 56.0 (2) 61.5 (2) 67.4 (2) 73.5 (2) 78.5 (2)
  Nom. 6°CWB kW 28.0 (2) 36.4 (2) 22.4 (2) 28.0 (2) 33.5 (2) 40.0 (2) 44.8 (2) 45.0 (2) 50.4 (2) 50.4 (2) 55.9 (2) 56.0 (2) 61.5 (2) 67.4 (2) 73.5 (2) 78.5 (2)
COP at nom. capacity 6°CWB KW/KW 3.66 (2) 3.76 (2) 3.83 (2) 3.45 (2) 3.46 (2) 3.57 (2) 3.72 (2) 3.52 (2) 3.61 (2) 3.66 (2) 3.60 (2) 3.37 (2) 3.46 (2) 3.62 (2) 3.52 (2) 3.49 (2)
SEER 7.62 7.49 7.35 7.14 7.21 7.73 7.40 7.10 7.26 7.09 7.27 6.63 7.17 7.16 7.48 7.15
SEER recommended combination 2 7.30 7.15 7.07 6.87 6.90 7.53 6.93 7.01 6.95 6.94 6.94 6.57 6.88 7.01 7.23 6.96
SEER recommended combination 3 7.61 7.57 7.49 7.15 7.41 7.78 7.31 7.15 7.30 7.11 7.48 6.64 7.28 7.29 7.61 7.26
SCOP 4.09 4.11 4.11 4.33 4.49 4.28 4.35 4.26 4.34 4.39 4.38 4.14 4.41 4.20 4.38 4.36
SCOP recommended combination 2 4.14 4.19 4.10 4.34 4.56 4.33 4.38 4.33 4.40 4.33 4.48 4.11 4.45 4.24 4.44 4.43
SCOP recommended combination 3 4.16 4.22 4.15 4.40 4.56 4.33 4.37 4.32 4.46 4.39 4.50 4.14 4.48 4.25 4.44 4.43
Space cooling A Condition (35°C - 27/19) EERd   3.81 3.46 3.25 3.26 3.24 3.26 3.25 3.23 3.26 2.73 3.24 2.57 3.25 3.24 3.25 3.23
    Pdc kW 28.0 36.4 22.4 28.0 33.5 40.0 44.8 45.0 50.4 50.4 55.9 56.0 61.5 67.4 73.5 78.5
  B Condition (30°C - 27/19) EERd   7.73 6.08 5.23 5.00 4.60 4.92 5.41 4.58 5.18 4.47 4.89 4.42 4.78 4.78 4.77 4.59
    Pdc kW 20.6 26.8 16.5 20.6 24.7 29.5 33.0 33.2 37.1 37.1 41.2 41.3 45.3 49.7 54.2 57.8
  C Condition (25°C - 27/19) EERd   8.99 9.04 9.11 8.50 8.45 8.74 9.11 8.25 8.76 8.15 8.70 7.70 8.47 8.52 8.61 8.33
    Pdc kW 13.5 18.0 10.6 13.3 15.9 18.9 21.2 21.3 23.9 23.9 26.5 26.5 29.1 31.9 34.8 37.2
  D Condition (20°C - 27/19) EERd   11.5 13.9 15.3 14.8 17.7 22.5 15.0 16.7 15.0 20.7 16.4 15.8 16.2 16.0 20.1 17.1
    Pdc kW 14.1 15.5 8.13 8.19 8.57 10.9 15.9 11.1 16.3 12.0 16.7 11.6 16.8 19.2 19.5 19.7
Space cooling recommended combination 2 A Condition (35°C - 27/19) EERd   3.67 3.36 3.23 3.23 3.00 3.23 3.14 3.06 3.23 2.64 3.09 2.52 3.10 3.11 3.12 3.03
    Pdc kW 28.0 36.4 22.4 28.0 33.5 40.0 44.8 45.0 50.4 50.4 55.9 56.0 61.5 67.4 73.5 78.5
  B Condition (30°C - 27/19) EERd   7.32 5.78 5.09 4.83 4.54 4.85 5.00 4.64 4.94 4.43 4.75 4.41 4.67 4.78 4.71 4.60
    Pdc kW 20.6 26.8 16.5 20.6 24.7 29.5 33.0 33.2 37.1 37.1 41.2 41.3 45.3 49.7 54.2 57.8
  C Condition (25°C - 27/19) EERd   8.54 8.53 8.55 8.06 7.94 8.38 8.36 8.11 8.27 7.87 8.17 7.41 8.00 8.25 8.17 8.04
    Pdc kW 13.3 17.8 10.6 13.3 15.9 18.9 21.2 21.3 23.9 23.9 26.5 26.5 29.1 31.9 34.8 37.2
  D Condition (20°C - 27/19) EERd   11.1 13.3 14.6 14.1 16.9 21.7 14.3 16.5 14.3 20.0 15.7 16.6 15.4 15.6 19.3 16.7
    Pdc kW 13.7 15.0 7.84 7.97 8.20 10.6 15.5 10.8 15.8 11.6 16.0 11.9 16.2 18.6 18.8 19.0
Space cooling recommended combination 3 A Condition (35°C - 27/19) EERd   3.71 3.41 3.22 3.27 3.23 3.30 3.18 3.04 3.25 2.66 3.27 2.50 3.25 3.13 3.27 3.12
    Pdc kW 28.0 36.4 22.4 28.0 33.5 40.0 44.8 45.0 50.4 50.4 55.9 56.0 61.5 67.4 73.5 78.5
  B Condition (30°C - 27/19) EERd   7.71 6.12 5.31 4.91 4.69 4.93 5.24 4.64 5.08 4.49 5.04 4.41 4.79 4.94 4.82 4.66
    Pdc kW 20.6 26.8 16.5 20.6 24.7 29.5 33.0 33.2 37.1 37.1 41.2 41.3 45.3 49.7 54.1 57.8
  C Condition (25°C - 27/19) EERd   8.99 9.22 9.41 8.59 8.82 8.84 9.04 8.50 8.94 8.22 9.03 7.71 8.71 8.77 8.83 8.64
    Pdc kW 13.5 18.1 10.6 13.3 15.9 18.9 21.2 21.3 23.9 23.9 26.5 26.5 29.1 31.9 34.8 37.2
  D Condition (20°C - 27/19) EERd   11.6 14.2 15.7 15.1 18.5 22.4 15.2 16.7 15.4 20.9 16.9 16.4 16.6 16.2 20.5 17.5
    Pdc kW 14.1 15.5 8.19 8.13 8.50 10.9 16.0 10.7 16.3 11.9 16.7 11.8 16.6 18.9 19.4 19.3
Space heating (Average climate) TBivalent COPd (declared COP)   2.69 2.74 2.80 2.28 2.38 2.57 2.87 2.53 2.51 2.36 2.55 2.23 2.33 2.62 2.48 2.46
    Pdh (declared heating cap) kW 16.0 21.7 13.7 16.0 18.4 20.6 23.2 23.2 27.9 27.9 31.0 31.0 34.4 36.9 39.0 41.6
    Tbiv (bivalent temperature) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  Space heating (Average climate)-=-E condition (-10°C) Space heating (Average climate)-=-E condition (-10°C)-=-COPd (declared COP)   2.69 2.74 2.80 2.28 2.38 2.57 2.87 2.53 2.51 2.36 2.55 2.23 2.33 2.62 2.48 2.46
    Space heating (Average climate)-=-E condition (-10°C)-=-Pdh (declared heating cap)-=-kW kW 16.0 21.7 13.7 16.0 18.4 20.6 23.2 23.2 27.9 27.9 31.0 31.0 34.4 36.9 39.0 41.6
  TOL Tol (temperature operating limit) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  A Condition (-7°C) COPd (declared COP)   3.00 3.03 3.06 2.67 2.84 2.94 3.18 2.87 2.87 2.70 2.95 2.60 2.76 2.94 2.89 2.85
    Pdh (declared heating cap) kW 14.2 19.2 12.1 14.2 16.3 18.2 20.5 20.5 24.7 24.7 27.4 27.4 30.4 32.6 34.5 36.8
  B Condition (2°C) COPd (declared COP)   4.37 4.02 3.81 4.23 4.15 3.86 4.17 3.93 4.20 4.19 4.09 3.84 4.19 3.89 3.99 4.03
    Pdh (declared heating cap) kW 8.60 11.7 7.38 8.62 9.89 11.1 12.5 12.5 15.0 15.0 16.7 16.7 18.5 19.9 21.0 22.4
  C Condition (7°C) COPd (declared COP)   4.70 5.11 5.27 5.70 6.32 6.31 5.45 6.21 5.60 6.22 5.90 5.89 6.02 5.82 6.32 6.26
    Pdh (declared heating cap) kW 7.17 8.40 4.76 5.54 6.36 7.13 8.05 8.03 9.66 9.66 10.7 10.7 11.9 12.8 13.5 14.4
  D Condition (12°C) COPd (declared COP)   5.57 6.47 7.04 7.92 9.14 6.68 6.93 6.04 7.49 6.85 8.06 7.70 8.49 6.47 7.76 7.33
    Pdh (declared heating cap) kW 8.74 8.93 4.51 5.46 5.52 5.15 9.04 5.07 9.97 6.24 10.0 7.34 11.0 9.58 10.7 10.6
Space heating (Average climate) recommended combination 2 TBivalent COPd (declared COP)   2.70 2.26 2.73 2.32 2.38 2.58 2.38 2.54 2.27 2.28 2.34 2.18 2.26 2.17 2.24 2.20
    Pdh (declared heating cap) kW 16.0 21.7 13.7 16.0 18.4 20.6 23.2 23.2 27.9 27.9 31.0 31.0 34.4 36.9 39.0 41.6
    Tbiv (bivalent temperature) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  TOL COPd (declared COP)   2.70 2.26 2.73 2.32 2.38 2.58 2.38 2.54 2.27 2.28 2.34 2.18 2.26 2.17 2.24 2.20
    Pdh (declared heating cap) kW 16.0 21.7 13.7 16.0 18.4 20.6 23.2 23.2 27.9 27.9 31.0 31.0 34.4 36.9 39.0 41.6
    Tol (temperature operating limit) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  A Condition (-7°C) COPd (declared COP)   3.02 3.05 3.00 2.62 2.83 2.95 3.18 2.89 2.86 2.62 2.96 2.54 2.73 2.93 2.89 2.86
    Pdh (declared heating cap) kW 14.2 19.2 12.1 14.2 16.3 18.2 20.5 20.5 24.7 24.7 27.4 27.5 30.4 32.6 34.5 36.8
  B Condition (2°C) COPd (declared COP)   4.43 4.12 3.80 4.24 4.26 3.89 4.18 3.96 4.27 4.07 4.21 3.79 4.25 3.90 4.06 4.09
    Pdh (declared heating cap) kW 8.64 11.7 7.45 8.61 9.89 11.1 12.5 12.5 15.0 15.0 16.7 16.7 18.5 19.9 21.0 22.4
  C Condition (7°C) COPd (declared COP)   4.76 5.24 5.35 5.79 6.39 6.45 5.57 6.41 5.78 6.19 6.07 5.98 6.10 5.97 6.42 6.40
    Pdh (declared heating cap) kW 7.31 8.54 4.76 5.54 6.36 7.14 8.08 8.04 9.65 9.65 10.7 10.7 11.9 12.8 13.5 14.4
  D Condition (12°C) COPd (declared COP)   5.62 6.58 7.04 7.91 9.39 6.94 6.97 6.47 7.59 8.15 8.30 7.81 8.60 6.72 8.03 7.72
    Pdh (declared heating cap) kW 8.87 9.17 4.71 5.60 5.80 5.33 9.24 5.36 10.3 7.68 10.5 7.69 11.4 10.1 11.1 11.2
Space heating (Average climate) recommended combination 3 TBivalent COPd (declared COP)   2.71 2.78 2.78 2.29 2.41 2.58 2.86 2.54 2.53 2.39 2.59 2.24 2.35 2.62 2.50 2.48
    Pdh (declared heating cap) kW 16.0 21.7 13.7 16.0 18.4 20.6 23.2 23.2 27.9 28.0 31.0 31.1 34.4 36.9 39.0 41.6
    Tbiv (bivalent temperature) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  TOL COPd (declared COP)   2.71 2.78 2.78 2.29 2.41 2.58 2.86 2.54 2.53 2.39 2.59 2.24 2.35 2.62 2.50 2.48
    Pdh (declared heating cap) kW 16.0 21.7 13.7 16.0 18.4 20.6 23.2 23.2 27.9 28.0 31.0 31.1 34.4 36.9 39.0 41.6
    Tol (temperature operating limit) °C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  A Condition (-7°C) COPd (declared COP)   3.03 3.07 3.05 2.68 2.85 2.96 3.17 2.88 2.91 2.73 2.99 2.60 2.77 2.95 2.91 2.87
    Pdh (declared heating cap) kW 14.2 19.2 12.1 14.2 16.3 18.2 20.5 20.5 24.7 24.8 27.5 27.5 30.5 32.7 34.6 36.9
  B Condition (2°C) COPd (declared COP)   4.48 4.14 3.86 4.32 4.24 3.89 4.19 3.95 4.35 4.25 4.22 3.88 4.28 3.92 4.05 4.08
    Pdh (declared heating cap) kW 8.61 11.7 7.39 8.62 9.89 11.1 12.5 12.5 15.0 15.0 16.7 16.7 18.5 19.9 21.0 22.4
  C Condition (7°C) COPd (declared COP)   4.76 5.25 5.35 5.80 6.43 6.43 5.52 6.34 5.77 6.39 6.07 6.07 6.12 5.93 6.43 6.38
    Pdh (declared heating cap) kW 7.28 8.49 4.75 5.55 6.36 7.15 8.04 8.03 9.67 9.66 10.7 10.7 11.9 12.8 13.5 14.4
  D Condition (12°C) COPd (declared COP)   5.62 6.64 7.14 8.02 9.37 6.84 6.94 6.44 7.69 5.48 8.32 6.15 8.65 6.75 7.95 7.68
    Pdh (declared heating cap) kW 8.85 9.13 4.65 5.56 5.67 5.29 9.17 5.32 10.2 5.80 10.3 5.91 11.2 9.97 11.0 11.0
Capacity range HP 10 13 8 10 12 14 16 16 18 18 20 20 22 24 26 28
Maximum number of connectable indoor units 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3)
Indoor index connection Min.   125 163 100 125 150 175 200 200 225 225 250 250 275 300 325 350
  Max.   325 423 260 325 390 455 520 520 585 585 650 650 715 780 845 910
Dimensions Unit Height mm     1,685 1,685 1,685 1,685   1,685   1,685   1,685
    Width mm     930 930 930 1240   1240   1240   1240
    Depth mm     765 765 765 765   765   765   765
Weight Unit kg     213 213 213 296   296   319   319
Fan External static pressure Max. Pa     78 78 78 78   78   78   78
Compressor Type       Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor   Hermetically sealed scroll compressor   Hermetically sealed scroll compressor   Hermetically sealed scroll compressor
Operation range Cooling Min. °CDB     -5 -5 -5 -5   -5   -5   -5
    Max. °CDB     46 46 46 46   46   46   46
  Heating Min. °CWB     -20 -20 -20 -20   -20   -20   -20
    Max. °CWB     16 16 16 16   16   16   16
Sound power level Cooling Nom. dBA 81.3 (5) 81.3 (5) 78.3 (5) 78.8 (5) 82.5 (5) 78.7 (5) 81.3 (5) 83.7 (5) 81.6 (5) 83.4 (5) 83.9 (5) 87.9 (5) 84.0 (5) 84.8 (5) 84.0 (5) 86.2 (5)
Sound pressure level Cooling Nom. dBA 59.3 (6) 59.3 (6) 56.3 (6) 58.0 (6) 60.8 (6) 58.1 (6) 59.3 (6) 61.4 (6) 60.2 (6) 63.0 (6) 62.1 (6) 67.0 (6) 62.6 (6) 62.6 (6) 62.7 (6) 64.1 (6)
Refrigerant Type   R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32
  GWP   675.0 675.0 675.0 675.0 675.0 675.0 675.0 675.0 675.0 675.0 675.0 675.0 675.0 675.0 675.0 675.0
  Charge tCO2Eq     6.08 6.08 6.08 7.16   7.16   7.16   7.16
  Charge kg     9.00 9.00 9.00 10.6   10.6   10.6   10.6
Piping connections Liquid Type   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
    OD mm 9.52 12.70 9.52 9.52 12.70 12.70 12.70 12.70 12.70 12.70 12.70 12.70 12.70 12.70 15.90 15.90
  Gas Type   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
    OD mm 19.1 22.2 19.1 19.1 22.2 22.2 22.2 22.2 22.2 22.2 28.6 28.6 28.6 28.6 28.6 28.6
  HP/LP gas OD mm 15.90 19.10 15.90 15.90 19.10 19.10 19.10 19.10 19.10 19.10 22.20 22.20 22.20 22.20 22.20 22.20
  Total piping length System Actual m 500 (7) 500 (7) 1,000 (7) 1,000 (7) 1,000 (7) 1,000 (7) 500 (7) 1,000 (7) 500 (7) 1,000 (7) 500 (7) 1,000 (7) 1000 (7) 1000 (7) 1000 (7) 1000 (7)
Standard Accessories Connection pipes 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
  Installation and operation manual 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Power supply Name   Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1
  Phase   3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~
  Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system.
  (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Sound power level is an absolute value that a sound source generates. (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Sound power level is an absolute value that a sound source generates. (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Sound power level is an absolute value that a sound source generates. (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of
  (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound power level is an absolute value that a sound source generates.
  (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Refer to refrigerant pipe selection or installation manual (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Refer to refrigerant pipe selection or installation manual (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Refer to refrigerant pipe selection or installation manual (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
  (7) - Refer to refrigerant pipe selection or installation manual (7) - Refer to refrigerant pipe selection or installation manual (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - Refer to refrigerant pipe selection or installation manual (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - Refer to refrigerant pipe selection or installation manual (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - Refer to refrigerant pipe selection or installation manual (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - Refer to refrigerant pipe selection or installation manual (7) - Refer to refrigerant pipe selection or installation manual (7) - Refer to refrigerant pipe selection or installation manual (7) - Refer to refrigerant pipe selection or installation manual
  (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
  (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
  (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
  (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - Maximum allowable voltage range variation between phases is 2%. (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - Maximum allowable voltage range variation between phases is 2%. (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - Maximum allowable voltage range variation between phases is 2%. (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%.
  (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Sound values are measured in a semi-anechoic room. (14) - Sound values are measured in a semi-anechoic room. (14) - Sound values are measured in a semi-anechoic room. (14) - Sound values are measured in a semi-anechoic room. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Sound values are measured in a semi-anechoic room. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Sound values are measured in a semi-anechoic room. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Sound values are measured in a semi-anechoic room. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (15) - Sound values are measured in a semi-anechoic room. (15) - Sound values are measured in a semi-anechoic room. (15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (15) - Sound values are measured in a semi-anechoic room. (15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (15) - Sound values are measured in a semi-anechoic room. (15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (15) - Sound values are measured in a semi-anechoic room. (15) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (15) - Sound values are measured in a semi-anechoic room. (15) - Sound values are measured in a semi-anechoic room. (15) - Sound values are measured in a semi-anechoic room. (15) - Sound values are measured in a semi-anechoic room.
  (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - Ssc: Short-circuit power (16) - Ssc: Short-circuit power (16) - Ssc: Short-circuit power (16) - Ssc: Short-circuit power (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - Ssc: Short-circuit power (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - Ssc: Short-circuit power (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - Ssc: Short-circuit power (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
  (17) - Ssc: Short-circuit power (17) - Ssc: Short-circuit power (17) - For detailed contents of standard accessories, see installation/operation manual (17) - For detailed contents of standard accessories, see installation/operation manual (17) - For detailed contents of standard accessories, see installation/operation manual (17) - For detailed contents of standard accessories, see installation/operation manual (17) - Ssc: Short-circuit power (17) - For detailed contents of standard accessories, see installation/operation manual (17) - Ssc: Short-circuit power (17) - For detailed contents of standard accessories, see installation/operation manual (17) - Ssc: Short-circuit power (17) - For detailed contents of standard accessories, see installation/operation manual (17) - Ssc: Short-circuit power (17) - Ssc: Short-circuit power (17) - Ssc: Short-circuit power (17) - Ssc: Short-circuit power
  (18) - For detailed contents of standard accessories, see installation/operation manual (18) - For detailed contents of standard accessories, see installation/operation manual (18) - Multi combination (10~28HP) data is corresponding with the standard multi combination (18) - Multi combination (10~28HP) data is corresponding with the standard multi combination (18) - Multi combination (10~28HP) data is corresponding with the standard multi combination (18) - Multi combination (10~28HP) data is corresponding with the standard multi combination (18) - For detailed contents of standard accessories, see installation/operation manual (18) - Multi combination (10~28HP) data is corresponding with the standard multi combination (18) - For detailed contents of standard accessories, see installation/operation manual (18) - Multi combination (10~28HP) data is corresponding with the standard multi combination (18) - For detailed contents of standard accessories, see installation/operation manual (18) - Multi combination (10~28HP) data is corresponding with the standard multi combination (18) - For detailed contents of standard accessories, see installation/operation manual (18) - For detailed contents of standard accessories, see installation/operation manual (18) - For detailed contents of standard accessories, see installation/operation manual (18) - For detailed contents of standard accessories, see installation/operation manual
  (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination         (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination   (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination   (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination   (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination