Specifications Table for FWE-CF

FWE02CF FWE03CF FWE04CF FWE06CF FWE07CF FWE08CF FWE10CF
Cooling capacity (standard conditions) Sensible capacity 4-pipe Fan speed 1 kW 0.92 (1) 1.41 (1) 1.70 (1) 2.80 (1) 2.96 (1) 3.70 (1) 4.66 (1)
    Low kW 1.13 (1) 1.68 (1) 1.96 (1) 3.16 (1) 3.54 (1) 4.32 (1) 5.35 (1)
    High kW 1.51 (1) 2.30 (1) 2.88 (1) 4.37 (1) 5.00 (1) 5.73 (1) 7.22 (1)
  Total capacity 4-pipe Fan speed 1 kW 1.25 (1) 1.91 (1) 2.29 (1) 3.78 (1) 3.99 (1) 5.00 (1) 6.29 (1)
    Low kW 1.53 (1) 2.31 (1) 2.65 (1) 4.40 (1) 4.81 (1) 5.86 (1) 7.35 (1)
    High kW 2.04 (1) 3.09 (1) 3.89 (1) 5.93 (1) 6.62 (1) 7.61 (1) 9.68 (1)
Heating capacity (standard conditions) Capacity 4-pipe Fan speed 1 kW 1.33 (3) 2.12 (3) 2.55 (3) 3.69 (3) 4.42 (3) 5.35 (3) 7.47 (3)
    Low kW 1.57 (3) 2.41 (3) 2.88 (3) 4.13 (3) 5.03 (3) 5.91 (3) 8.39 (3)
    High kW 2.08 (3) 3.11 (3) 4.14 (3) 5.43 (3) 6.69 (3) 7.50 (3) 10.90 (3)
Power input Fan speed 1 kW 0.030 (4) 0.040 (4) 0.040 (4) 0.060 (4) 0.090 (4) 0.100 (4) 0.120 (4)
  Low kW 0.034 (4) 0.047 (4) 0.050 (4) 0.073 (4) 0.105 (4) 0.133 (4) 0.145 (4)
  High kW 0.046 (4) 0.069 (4) 0.083 (4) 0.119 (4) 0.163 (4) 0.181 (4) 0.230 (4)
Dimensions Unit Height mm 253 253 253 253 253 253 253
    Width mm 590 590 590 590 590 590 590
    Depth mm 705 875 1010 1210 1460 1560 1820
Weight Unit kg 18.1 21.6 25.3 30.1 39.7 41.4 48.9
Casing Colour   Metal Metal Metal Metal Metal Metal Metal
Fan Air flow rate Fan speed 1 m³/h 142 (4) 256 (4) 257 (4) 414 (4) 569 (4) 684 (4) 804 (4)
    Low m³/h 232 (4) 371 (4) 377 (4) 618 (4) 846 (4) 1001 (4) 1199 (4)
    High m³/h 416 (4) 626 (4) 835 (4) 1193 (4) 1548 (4) 1742 (4) 2166 (4)
  Available static pressure Fan speed 1 Pa 4 7 7 4 30 30 30
    Low Pa 18 35 38 45 48 48 48
    High Pa 37 63 63 65 67 67 70
Total sound power level Fan speed 1 dBA 31.0 (5) 38.0 (5) 32.0 (5) 39.0 (5) 38.0 (5) 41.0 (5) 40.0 (5)
  Low dBA 42.0 (5) 49.0 (5) 40.0 (5) 48.0 (5) 51.0 (5) 50.0 (5) 54.0 (5)
  High dBA 55.0 (5) 61.0 (5) 58.0 (5) 62.0 (5) 62.0 (5) 64.0 (5) 68.0 (5)
Sound pressure level Fan speed 1 dBA 21.0 (6) 28.0 (6) 22.0 (6) 29.0 (6) 28.0 (6) 31.0 (6) 30.0 (6)
  Low dBA 32.0 (6) 39.0 (6) 30.0 (6) 38.0 (6) 41.0 (6) 40.0 (6) 44.0 (6)
  High dBA 45.0 (6) 51.0 (6) 48.0 (6) 52.0 (6) 52.0 (6) 54.0 (6) 58.0 (6)
Water flow Cooling Fan speed 1 l/h 214 (1) 328 (1) 393 (1) 651 (1) 686 (1) 859 (1) 1081 (1)
    Low l/h 257 (1) 388 (1) 447 (1) 743 (1) 807 (1) 987 (1) 1240 (1)
    High l/h 344 (1) 520 (1) 654 (1) 1002 (1) 1111 (1) 1282 (1) 1624 (1)
  Heating Fan speed 1 l/h 114 (3) 182 (3) 220 (3) 317 (3) 380 (3) 460 (3) 642 (3)
    Low l/h 135 (3) 211 (3) 248 (3) 360 (3) 440 (3) 520 (3) 735 (3)
    High l/h 178 (3) 276 (3) 356 (3) 479 (3) 592 (3) 661 (3) 963 (3)
  Water pressure drop Cooling Fan speed 1 kPa 6.00 (2) 12.00 (2) 11.00 (2) 19.00 (2) 7.00 (2) 9.00 (2) 14.00 (2)
      Low kPa 8.05 (2) 16.38 (2) 13.67 (2) 24.31 (2) 8.54 (2) 10.68 (2) 17.52 (2)
      High kPa 12.04 (2) 28.70 (2) 25.94 (2) 42.89 (2) 12.65 (2) 16.05 (2) 28.13 (2)
    Heating Fan speed 1 kPa 7.00 (3) 11.00 (3) 17.00 (3) 30.00 (3) 12.00 (3) 16.00 (3) 24.00 (3)
      Low kPa 7.61 (3) 12.88 (3) 19.88 (3) 38.73 (3) 13.85 (3) 19.12 (3) 30.52 (3)
      High kPa 9.56 (3) 19.12 (3) 34.16 (3) 68.07 (3) 21.05 (3) 26.79 (3) 48.75 (3)
Allowed water temperature Cooling Min. °C 3 3 3 3 3 3 3
    Max. °C 70.0 70.0 70.0 70.0 70.0 70.0 70.0
  Heating Min. °C 3.00 3.00 3.00 3.00 3.00 3.00 3.00
    Max. °C 70.000 70.000 70.000 70.000 70.000 70.000 70.000
Power supply Frequency Hz 50 50 50 50 50 50 50
Current input Fan speed 1 A 0.128 0.177 0.188 0.271 0.400 0.456 0.540
  Low A 0.150 0.208 0.217 0.325 0.472 0.523 0.648
  High A 0.206 0.309 0.372 0.533 0.731 0.811 1.031
Notes (1) - Inlet/outlet water temperature 7/12 °C; inlet air temperature 27°C DB 19°C WB (1) - Inlet/outlet water temperature 7/12 °C; inlet air temperature 27°C DB 19°C WB (1) - Inlet/outlet water temperature 7/12 °C; inlet air temperature 27°C DB 19°C WB (1) - Inlet/outlet water temperature 7/12 °C; inlet air temperature 27°C DB 19°C WB (1) - Inlet/outlet water temperature 7/12 °C; inlet air temperature 27°C DB 19°C WB (1) - Inlet/outlet water temperature 7/12 °C; inlet air temperature 27°C DB 19°C WB (1) - Inlet/outlet water temperature 7/12 °C; inlet air temperature 27°C DB 19°C WB
  (2) - Heating: indoor temp. 20°CDB, 15°CWB; entering water temp. 45°C, water temperature drop 5K. (2) - Heating: indoor temp. 20°CDB, 15°CWB; entering water temp. 45°C, water temperature drop 5K. (2) - Heating: indoor temp. 20°CDB, 15°CWB; entering water temp. 45°C, water temperature drop 5K. (2) - Heating: indoor temp. 20°CDB, 15°CWB; entering water temp. 45°C, water temperature drop 5K. (2) - Heating: indoor temp. 20°CDB, 15°CWB; entering water temp. 45°C, water temperature drop 5K. (2) - Heating: indoor temp. 20°CDB, 15°CWB; entering water temp. 45°C, water temperature drop 5K. (2) - Heating: indoor temp. 20°CDB, 15°CWB; entering water temp. 45°C, water temperature drop 5K.
  (3) - Heating: indoor temp. 20°CDB, 15°CWB; entering water temp. 65°C, water temperature drop 10K. (3) - Heating: indoor temp. 20°CDB, 15°CWB; entering water temp. 65°C, water temperature drop 10K. (3) - Heating: indoor temp. 20°CDB, 15°CWB; entering water temp. 65°C, water temperature drop 10K. (3) - Heating: indoor temp. 20°CDB, 15°CWB; entering water temp. 65°C, water temperature drop 10K. (3) - Heating: indoor temp. 20°CDB, 15°CWB; entering water temp. 65°C, water temperature drop 10K. (3) - Heating: indoor temp. 20°CDB, 15°CWB; entering water temp. 65°C, water temperature drop 10K. (3) - Heating: indoor temp. 20°CDB, 15°CWB; entering water temp. 65°C, water temperature drop 10K.
  (4) - Airflow value measurements are performed at 20C (DB) /15 C(WB) condition. (4) - Airflow value measurements are performed at 20C (DB) /15 C(WB) condition. (4) - Airflow value measurements are performed at 20C (DB) /15 C(WB) condition. (4) - Airflow value measurements are performed at 20C (DB) /15 C(WB) condition. (4) - Airflow value measurements are performed at 20C (DB) /15 C(WB) condition. (4) - Airflow value measurements are performed at 20C (DB) /15 C(WB) condition. (4) - Airflow value measurements are performed at 20C (DB) /15 C(WB) condition.
  (5) - Sound power level according to ISO3741 (5) - Sound power level according to ISO3741 (5) - Sound power level according to ISO3741 (5) - Sound power level according to ISO3741 (5) - Sound power level according to ISO3741 (5) - Sound power level according to ISO3741 (5) - Sound power level according to ISO3741
  (6) - The sound pressure level is measured via a microphone at 1m distance of the unit. (6) - The sound pressure level is measured via a microphone at 1m distance of the unit. (6) - The sound pressure level is measured via a microphone at 1m distance of the unit. (6) - The sound pressure level is measured via a microphone at 1m distance of the unit. (6) - The sound pressure level is measured via a microphone at 1m distance of the unit. (6) - The sound pressure level is measured via a microphone at 1m distance of the unit. (6) - The sound pressure level is measured via a microphone at 1m distance of the unit.