Specifications Table for FTXM-N / RXM-M9

FTXM20N2V1B / RXM20M3V1B9 FTXM25N2V1B / RXM25M3V1B9 FTXM35N2V1B / RXM35M3V1B9
Cooling capacity Min. kW 1.3 1.3 1.4
  Max. kW 2.6 3.2 4.0
  Nom. kW 2.0 2.5 3.4
Space cooling SEER   8.53 8.52 8.51
  Annual energy consumption kWh/a 83 103 140
  Capacity Pdesign kW 2.00 2.50 3.40
  Energy efficiency class   A+++ A+++ A+++
Space heating (Average climate) Capacity Pdesign kW 2.30 2.40 2.50
  SCOP/A   5.10 5.10 5.10
  Energy efficiency class   A+++ A+++ A+++
  Pdh Heating capacity at -10° kW 2.24 2.30 2.35
  Annual energy consumption kWh/a 632 659 686
Nominal efficiency Annual energy consumption kWh 220 280 400
  EER   4.57 4.50 4.23
  COP   5.00 5.00 4.04
  Energy labeling Directive Cooling   A A A
    Heating   A A A
Heating capacity Nom. kW 2.50 2.80 4.00
  Min. kW 1.30 1.30 1.40
  Max. kW 3.50 4.70 5.20
Notes (1) - See separate drawing for electrical data (1) - See separate drawing for electrical data (1) - See separate drawing for electrical data
  (2) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (3) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (3) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (3) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.