Specifications Table for FBA-A(9) / RZQSG-L3/9V1

FBA35A2VEB9 / FBA35A2VEB9 / RZQSG71L3V1B FBA71A2VEB9 / RZQSG71L3V1B FBA100A2VEB / RZQSG100L9V1B FBA35A2VEB9 / FBA35A2VEB9 / FBA35A2VEB9 / RZQSG100L9V1B FBA50A2VEB9 / FBA50A2VEB9 / RZQSG100L9V1B FBA35A2VEB9 / FBA35A2VEB9 / FBA35A2VEB9 / FBA35A2VEB9 / RZQSG125L9V1B FBA50A2VEB9 / FBA50A2VEB9 / FBA50A2VEB9 / RZQSG125L9V1B FBA60A2VEB9 / FBA60A2VEB9 / RZQSG125L9V1B FBA125A2VEB / RZQSG125L9V1B FBA140A2VEB / RZQSG140L9V1B
Cooling capacity Nom. kW 6.80 6.80 9.50 9.50 9.50 12.00 12.00 12.00 12.00 13.40
Space cooling SEER   5.10 5.84 5.61 5.10 5.10 4.80 4.80 4.80 5.47 5.23
  Annual energy consumption kWh/a 467 408 593 652 652 875 875 875 768 1,537
  Capacity Pdesign kW 6.80 6.80 9.50 9.50 9.50 12.00 12.00 12.00 12.00 13.40
  Energy efficiency class   A A+ A+ A A B B B A
Space heating (Average climate) Capacity Pdesign kW 6.00 6.00 7.60 7.60 7.60 7.60 7.60 7.60 7.60 11.57
  SCOP/A   3.80 4.01 4.15 3.80 3.80 3.80 3.80 3.80 4.01 3.81
  Energy efficiency class   A A+ A+ A A A A A A+
  Annual energy consumption kWh/a 2,211 2,095 2,564 2,800 2,800 2,800 2,800 2,800 2,653 4,255
Nominal efficiency EER   3.15 3.43 3.35 3.28 3.06 3.04 2.94 2.83 3.23 2.28
Notes (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
  (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range
  (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data
Nominal efficiency Annual energy consumption kWh   991 1,418   1,552 1,974 2,041 2,120 1,858
  COP     3.92 3.67   3.30 3.35 3.30 3.26 3.63 3.40
  Energy labeling Directive Cooling     A A   B B C C A
    Heating     A A   C C C C A
Heating capacity Nom. kW   7.50 10.80   10.80 13.50 13.50 13.50 13.50 15.50